Current Transformer Accuracy Classes

Home Technical

Current Transformer Accuracy Classes


Current Transformer Accuracy classes according to IEC 61689-2

Class

For burdens

Limits of errors

Application

at % rated current

Ratio error %

Phase

displacement Minutes

0.1

25-100% of

rated burden

5

0.4

15

Laboratory

20

0.20

8

100

0.1

5

120

0.1

5

0.2

25-100% of

rated burden

<15 VA

1 VA-100%

5

0.75

30

Precision revenue metering

20

0.35

15

100

0.2

10

120

0.2

10

0.2S

25-100% of

rated burden

<15 VA

1 VA-100%

1

0.75

30

Precision revenue metering

5

0.35

15

20

0.2

10

100

0.2

10

120

0.2

10

0.5

 

25-100% of

rated burden

5

1.5

90

Standard commercial metering

20

0.75

45

100

0.5

30

120

0.5

30

0.5S

25-100% of

rated burden

1

1.5

90

Precision revenue metering

5

0.75

45

20

0.5

30

100

0.5

30

120

0.5

30

1.0

25-100% of

rated burden

5

3.0

180

Industrial

grade meters

20

1.5

90

100

1.0

60

120

1.0

60

3.0

50-100%

50

3.0

-

Instruments

120

3.0

-

5.0

50-100%

50

5.0

-

Instruments

120

5.0

-

5P and 5PR

100%

100

1.0

60

Protection

ALF x In

5

-

10P and 10PR

100%

100

3.0

-

Protection

ALF x In

10

-

PX

Ek, Ie, Rct 

-

-

-

Protection

1) PF of secondary burden 0.8 (for 5 VA burden and lower PF = 1.0)

2) Composite error

3) Remanence factor (Kr) shall not exceed 10% after 3 minutes

4) Rated knee point e.m.f. (Ek). The minimum sinusoidal e.m.f. (r.m.s.) at rated power frequency when applied to the secondary terminals of the transformer, all other terminals being open-circuited, which when increased by 10% causes the r.m.s. excitation current to increase by no more than 50%.

Note! The actual knee point e.m.f. will be the rated knee point e.m.f.

5) Rct = CTs secondary resistance at 75 ℃.

 

Current Transformer Accuracy classes according to IEEE C57.13

Class

Error limits (the limits are valid for any of the standard burdens below)

Times rated current

Power error

%

Designation

Ohm

PF

Application

0.15

1.0

0.15

B-0.1

 

B-0.2

 

B-0.5

 

B-0.9

 

B-1.8

0.1

 

0.2

 

0.5

 

0.9

 

1.8

0.9

High-accuracy metering

0.05

0.30

0.15S

1.0

0.15

0.05

0.15

0.3

1.0

0.3

Metering

0.1

0.6

0.6

1.0

0.6

0.1

1.2

1.2

1.0

1.2

0.1

2.5

 

 

Class

Times rated current

Ratio error %

Secondary terminal voltage

Designation

PF

Application

Rated current

Low rated current

C100

T100

20

3

10

100

B-1.0

0.5

Protection

C200

T200

20

3

10

200

 

B-2.0

C400

T400

20

3

10

400

 

B-4.0

C800

T800

20

3

10

800

B-8.0

X

-

1

-

Es, Ie, Rct


1) Class C is used for cores with evenly distributed winding, i.e. when the leakage flux is negligible.

Class T is valid for CTs in which the leakage flux in the core of the transformer has an appreciable effect on the ratio.

2) Rated knee point voltage Es; specified in IEEE C57.13 -2008 6.10.2