Voltage Transformer Accuracy Classes

Home Technical

Voltage Transformer Accuracy Classes


Voltage Transformer Accuracy classes according to IEC 61689-3

Class

Range

Limits of errors

Application

Burden %

Voltage %

Ratio %

Phase

displacement Minutes

0.1

25-100 *)

80-120

0.1

5

Laboratory

0.2

25-100 *)

80-120

0.2

10

Precision and revenue

metering

0.5

25-100 *)

80-120

0.5

20

Standard revenue

metering

1.0

25-100 *)

80-120

1.0

40

Industrial grade

meters

3.0

25-100 *)

80-120

3.0

-

Instruments

3P

25-100 *)

5-FV **)

3.0

120

Protection

6P

25-100 *)

5-FV **)

6.0

240

Protection

*) For burdens<10 VA, 0 - 100%, PF = 1

**) FV = Voltage factor

 

Voltage Transformer Accuracy classes according to IEEE C57.13

Class

Range

Power error at

metered load PF 0.6-1.0%

Application

Burden %

Voltage %

0.15

0-100

90-110

0.15

High-accuracy metering

0.3

0-100

90-110

0.3

Revenue metering

0.6

0-100

90-110

0.6

Standard metering

1.2

0-100

90-110

1.2

Relaying

1.2R

0-100

90

1.2




25

3

Relaying CCVT



5

5


 

Standard burdens

VA

PF


M

35

0.20


W

12.5

0.10


X

25

0.70


Y

75

0.85


Z

200

0.85


ZZ

400

0.85