145 kV Current Transformer (Hair-pin Type)

Home Technical

145 kV Current Transformer (Hair-pin Type) is a high-voltage outdoor instrument transformer used in 132 kV and 145 kV air-insulated substations (AIS). It accurately converts high primary currents into standardized secondary currents (1 A or 5 A) for protective relays, energy metering, fault recording, and substation automation. The hair-pin type features an integral U-shaped primary conductor that forms a single-turn primary winding, providing high mechanical strength, excellent insulation performance, and reliable operation.

 

Working Principle

The 145 kV hair-pin type current transformer operates on the principle of electromagnetic induction.

When alternating current flows through the U-shaped primary conductor, an alternating magnetic flux is produced in the magnetic core. This changing flux induces a proportional current in the secondary winding while maintaining electrical isolation between the primary and secondary circuits.

 

Construction

A typical 145 kV hair-pin type current transformer consists of:

·Integral U-shaped copper or aluminum primary conductor

·High-permeability toroidal magnetic core

·Multiple secondary windings for metering and protection

·Oil-paper insulation system (most common)

·Porcelain or composite external insulator

·Oil expansion chamber or stainless-steel bellows

·Secondary terminal box

·Grounding terminal

·Galvanized steel support base

·Stainless steel nameplate

 

Features

·Single-turn hair-pin primary conductor.

·Excellent measurement accuracy.

·Multiple independent secondary cores.

·High insulation performance for 145 kV systems.

·High thermal and dynamic short-circuit withstand capability.

·Weather-resistant outdoor construction.

·Low partial discharge characteristics.

·Long service life with minimal maintenance.

 

Typical Ratings

·Highest system voltage: 145 kV

·Rated frequency: 50 or 60 Hz

·Primary current: 200–4000 A

·Secondary current: 1 A or 5 A

·Metering accuracy class: 0.1, 0.2, 0.2S, 0.5, 0.5S

·Protection accuracy class: 5P10, 5P20, 10P10, PX, TPX, TPY, TPZ

·Rated burden: 10–60 VA

·Lightning impulse withstand: Typically 650 kV

·Power-frequency withstand: Typically 275 kV (1 min)

·Installation: Outdoor AIS

 

Advantages

·High accuracy for both protection and revenue metering.

·Excellent insulation coordination for 132/145 kV systems.

·Robust single-turn primary conductor provides high mechanical strength.

·Multiple secondary cores support separate metering and protection functions.

·High resistance to thermal and mechanical stresses during short circuits.

·Reliable long-term performance under outdoor environmental conditions.

 

Limitations

·Oil-filled units require periodic inspection of oil condition, seals, and insulation integrity.

·Larger and heavier than medium-voltage resin-cast CTs.

·Requires adequate structural support during installation.

·The secondary winding must never be open-circuited while the primary is energized, because dangerous voltages can be induced across the secondary terminals.

 

Applications

145 kV hair-pin type current transformers are widely used in:

·132 kV and 145 kV transmission substations

·Transmission line bays

·Power transformer protection

·Busbar differential protection

·Circuit breaker bays

·Revenue and utility metering

·Industrial high-voltage substations

·Renewable energy grid substations

·Switching stations

 

Typical Secondary Core Arrangement

Core 1 Revenue metering  0.2S

Core 2 Operational metering 0.5

Core 3 Overcurrent and earth-fault protection 5P20

Core 4 Busbar or transformer differential protection PX / TPX / TPY / TPZ

 

Typical Uses

The 145 kV Hair-pin Type Current Transformer is widely deployed in 132 kV and 145 kV air-insulated substations for:

·Current measurement for supervisory control and data acquisition (SCADA)

·Revenue and utility energy metering

·Overcurrent and earth-fault protection

·Transformer and busbar differential protection

·Fault recording and disturbance monitoring

·Grid monitoring and substation automation

 

Its integral single-turn primary conductor, high dielectric strength, multiple secondary cores, and excellent measurement accuracy make it a dependable solution for modern high-voltage transmission systems where reliability, safety, and precision are critical.