Dissolved Gas Analysis (DGA) of Transformer Oil

Home Technical

Dissolved Gas Analysis (DGA) of Transformer Oil


Probability Norms (90%) (ANSI / IEEE C57.104-1991) for mineral oil filled transformers

Gas

Symbol

Normal Content

Generating Conditions (excess)

Key combustible Gases

ACETYLENE

C2H2

35 ppm

High Energy Arcing

HYDROGEN

 

H2

 

100 ppm

Corona (Partial (Discharge)

Electrolysis of Free Water 

Arcing (If Acetylene is also present)

METHANE

CH4

120 ppm

Generalized Overheating

ETHANE

C2H6

65 ppm

Generalized Overheating

ETHYLENE

C2H4

10 ppm

Hot Spot

Severe Localized Overheating

CARBON MONOXIDE

CO

350 ppm

Aging/Thermal Decomposition of Cellulose

Non combustible Gases

NITROGEN

 

N

Less than 5% of total

Normal Operation

Greater than 5%

Check for tightness of Nitrogen Seal

CARBON

DIOXIDE: Check Ratio of CO2/CO

 

CO2 CO

Ratio less than 7 -

Cellulose Breakdown

Ratio greater that 7

Normal

CO > 500

CO2 > 500

To improve certainty factor