Home Product Transformer Distribution Transformer

TransformerAmorphous Alloy Transformer

General Description
  • IEC 60076, ANSI/IEEE Std C57.12, NEMA

  • ISO 9001, KEMA, CESI, CE, TUV, UL, ASTA

  • Mineral Oil / Vegetable Oil (FR3), Free PCB

  • High magnetic susceptibility, Low coercivity

  • Low loss and Low magnetizing current, Higher stability

  • Seismic design, ETGI-1.020, IEEE Std 693, NCh2369

  • Structural design, ASTM A325, ANSI/AISC 360, AWS D1.1

  • High altitude correction per IEC 60076 & IEEE C57.12, ~ 5000m

Typical Specification

12kV Three-phase Two-winding Amorphous Alloy Transformer with NLTC

Rated

 Capacity

(kVA)

Voltage and tapping range(kV)

Vector

group

No-load

loss (W)

On-load

loss (W)

Impedance

(%)

No-load

current

(%)

Weight (kg)

Overall Dimension (mm)

Trail

Distance (mm)

HV

LV

L x W x H

30

7.2±2×2.5%

 

12±2×2.5%

 

13.2±2×2.5%

 

0.4

Dyn11

33

630

4.0

1.5

380

1050x650x780

550x550

50

43

910

1.2

510

1200x720x870

550x660

63

50

1090

1.0

600

1260x780x890

550x660

80

60

1310

0.9

645

1310x730x915

550x660

100

75

1580

0.8

720

1400x860x920

550x660

125

85

1890

0.6

850

1410x890x925

550x660

160

100

2310

0.6

900

1420x910x930

660x660

200

120

2730

0.6

940

1430x935x980

660x660

250

140

3200

0.6

1180

1535x930x1025

660x660

315

170

3830

0.5

1370

1595x925x1050

820x660

400

200

4520

0.5

1530

1610x905x1100

820x660

500

240

5410

0.5

1830

1690x935x1150

820x660

630

320

6200

4.5

0.3

2220

1800x950x1230

1070x660

800

380

7500

0.3

2590

1800x1100x1250

1070x660

1000

450

10300

0.3

3060

1900x1130x1290

1070x820

1250

530

12000

0.2

3600

2000x1190x1360

1070x820

1600

630

14500

0.2

4250

2130x1265x1450

1070x820