General rating (Circuit Breaker + Disconnector + Earthing Switch) |
Reference standard | IEC/IEEE |
Voltage | 72.5 kV |
Withstand voltage |
|
- Short-duration power-frequency, phase-to-earth / across isolating distance | 140/160 kV |
- Lightning impulse (BIL), phase-to-earth / across isolating distance | 325/375 kVp |
Frequency | 50/60 Hz |
Continuous current | 630/1250/2000A |
Short-time withstand current | 25/31.5 kA |
Peak withstand current | 63/80 kAp |
Duration of short-circuit | 3s |
Internal Arc Class | IAC A (FLR) 31.5kA/0.5s |
Installation | Indoor |
Ambient temperature range | down to -30 / up to +40 °C |
Circuit-breaker rating (Vacuum Interrupter) |
|
Short-circuit breaking current | 25/31.5 kA |
Short-circuit making current | 63/80 kAp |
Rated single capacitor bank breaking current | 630A |
Rated back to back capacitor bank breaking current | 400A |
Operating sequence | O-0.3s-CO-3 min-CO |
Drive type (three-phase or single-phase) | Spring-operated mechanism |
Mechanical endurance | M2 class |
Capacitive switching | C2 class |