Home Product Switchgear Gas Insulated Ring Main Unit (RMU)

SwitchgearGas Insulated Ring Main Unit (RMU) 36kV

General Description
  • IEC 62271, ANSI/IEEE Std C37, NEMA

  • ISO 9001, KEMA, CESI, CE, TUV, UL, ASTA

  • Seismic design, ETGI-1.020, IEEE Std 693, NCh2369

  • Structural design, ASTM A325, ANSI/AISC 360, AWS D1.1

  • High altitude correction per IEC 62271 & IEEE C37, ~ 5000m

  • High reliability, smart, compact and economic switchgear solutions

  • Modular design and flexible configuration for both side extensible design

  • Enhanced personnel safety and low maintenance for critical power application

Typical Specification

Gas Insulated Ring Main Unit (RMU) 36kV

General rating


Rated voltage

36/38kV

Power frequency withstand voltage (1min)


Phase to phase/Phase to earth

70kV

Between isolating distance

80kV

Lightning impulse withstand voltage (BIL)


Phase to phase/Phase to earth

170kV

Between isolating distance

185kV

Rated frequency

50/60Hz

Internal arc classification (IAC)

AFLR 20kA/1s

Degree of protection external  

IP4X  

Degree of protection gas tank

IP67

Service continuity of the switchgear

LSC2

Humidity condition

100%

Temperature condition

-25~+40

Busbar system


Rated normal current

630A, 1250A

Rated short-time withstand current

20kA/3s, 25kA/3s

Rated peak withstand current

50kA, 63kA

Load break switche panel


Rated normal current

630A

Rated short-circuit making current

50kA

Rated short-time withstand current

20kA/3s

Mechanical endurance class (Lood break switch)

M1 5000 times

Mechanical endurance class (Earthing switch)

M1 2000 times

Electrical endurance class (active load breaking capacity 630A)

E3  

Cable-charging breaking capacity

40A

Circuit-breaker panel


Rated normal current

630A, 1250A

Rated breaking current

20kA, 25kA

Rated short-circuit making current

50kA, 63kA

Rated capacitive switching current class

C2

Mechanical endurance class (Circuit-breakers)

M2 10000times

Mechanical endurance class (Earthing switch)

M1 3000 times

Electrical endurance class

E2

Rated short-time withstand current

20kA/3s, 25kA/3s

Mechanism type

O - 0.3s - CO - 180s - CO

Switch-fuse combination panel


Normal current of load-break switch

630A

Normal current with fuses

80A

Rated breaking current

31.5kA

Rated short-circuit making current

80kA

Rated transfer current

600A