Gas Insulated MV Switchgear (C-GIS) 24kV

General rating


Rated voltage

24kV

Rated frequency

50/60Hz

Power frequency withstand voltage (1 min)

50kV

Lightning impulse withstand voltage (BIL)

125kV

Internal arc class

AFLR 31.5kA/1s

Loss of service continuity category

LSC2B

Accessibility of compartments


Circuit breaker compartment

Interlocked-controlled

Busbar compartmen

Tool-based/non-accessible

Cable compartment

Tool-based or Interlock-controlled

External degree of protection

IP4X

Primary system degree of protection

IP65

Installation

Indoor

Busbar system


Rated normal current

630A, 1250A, 1600A, 2000A, 2500A

Rated short-time withstand current

25kA/3s or 31.5kA/3s

Rated peak withstand current

63kA or 80kA

Circuit breaker ratings


Rated normal current

630A, 1250A, 1600A, 2000A, 2500A

Rated short-circuit breaking current

25kA or 31.5kA

Rated short-circuit making current

63kA or 80kA

Rated short-time withstand current

25kA/3s or 31.5kA/3s

Breaking number of short-circuit current

30 times

Rated operating sequence

O-0.3s-CO-180s-CO

Circuit breaker class

E2/M2/C2

Mechanical endurance

10000 times