AC Input |
|
Voltage range (VAC) | 380V±20% |
Frequency range | 50Hz±10% or 60Hz±10% |
DC Output |
|
Rated voltage (VDC) | 220/110V |
Voltage regulation range (VDC) | 180-286V |
Rated current (ADC) | 5-200A |
Output current limiting range | 5%-110% |
Regulating voltage accuracy | ≤0.5% |
Regulating current accuracy | ≤0.5% |
Ripple coefficient | ≤0.1% |
Conversion efficiency (full load output) | ≥94 |
Dynamic response (load 20% -30%) | Recovery time ≤ 200 μ S, overshoot ≤ ± 2% |
Ambient condition |
|
Insulation strength | 2KVac 1min |
Noise (1m) | ≤55dB |
Working environment temperature | -5℃~+45℃ |
Transportation and storage temperature | -40~70℃ |
humidity | 0-90%, No condensation |
General rating |
|
Protection function | Output overvoltage protection, output current limiting protection, output short circuit protection, over temperature protection, module parallel protection, over current protection |
Lead–acid battery (VRLA) | 7AH, 17AH, 40AH, 65AH, 100AH, 200AH, 300AH, 400AH. .500AH, 600AH, 800AH, 1000AH, 1500AH,.2000AH, 3000AH |
Ni-Cd Battery | 100AH, 200AH, 300AH, 400AH. .500AH, 600AH, 800AH, 1000AH, 1500AH,.2000AH, 3000AH |
Typical dimension | 2260×800×600mm 2260×800×800mm |