Home Product MV Motor & Drive MV Motor

MV Motor & DriveMV Motor

General Description
  • IEC 60034, IEC 60072, EN60034-1, NEMA MG1, ISO 9001

  • Seismic design, ETGI-1.020, IEEE Std 693, NCh2369

  • Structural design, ASTM A325, ANSI/AISC 360, AWS D1.1

  • High altitude correction per IEC & IEEE & NEMA, ~ 5000m

  • Typical application for Oil & Gas, Petrochemical, Mining, Metallurgy, Nuclear power 

  • Optional: Stator Winding/Bearing RTD, Vibration probe, Transmitter, Neutral terminal box, EXPO purging unit

Typical Specification

MV/HV CACA Cooling TEFC Motor

General Rating

MV/HV motors for hazardous and safe areas

Output

185-20000kW

Frame size

H315-630

Speed

3000, 1500, 1000, 750, 600, 500, 428, 375, 300 RPM

Mechanical Protection

Air to air cooling, IP 55 enclosure as standard.

Torque Design

N Design

Voltage

3/3.3/4.16/5.5/6/6.6/10/11/13.8kV, 50/60Hz,

Certification

IECEx/ATEX certificate for hazardous area.

Frequency

Dual frequency 50/60Hz, VFD as option.

Server Factor

Service factor 1.0 as standard,

Duty

S1/Continuous.

Enclosure

Fabrication steel enclosure including frame, end-shield, terminal box.

Mounting

B3, B35 or V1.

Anti-corrosion

Epoxy anti-corrosion coating on all internal metal surfaces

Ambient Temperature

Ambient temperature -40 to +60 deg C as standard.

Sea Level

Sea level 1000m as standard.

Bearing and Lubrication

Sleeve bearings for H500 & above 2pole and H630 4pole motors , anti-frication bearings for others.

The pressure grease relief valve enabling re-lubrication of the bearings without stopping the motor.

Vibration

As per 60034-14.

Gas groups

IIA/IIB/IIC, both Zone 1 & 2,

Temperature group

T3 as standard.

Grounding

Grounding provisions inside terminal box plus external grounding provisions on frame

Nameplate

Stainless steel engraved nameplate with nominal efficiency and power factor data included

Variable Frequency(If required)

0-60Hz for 2pole 50Hz motors.

0-100Hz for 4pole and above 50Hz motors.

Stator

20 years design life.

High quality low losses silicon electrical steel.

Class F insulation system with Class B temperature rise, VPI treated.

Class H insulation available on request;

Temperature rise class B

 

Rotor

Die cast aluminum rotor as standard and cooper bar rotor as option, dynamically balanced.

High quality round steel shaft. Special steel available on request.

Non sparking fan

Low vibration/noise;

Terminal box(es)

Oversized to facility cable connection;

Rotatable 90 degrees;

Test

Standard type/routine test on each motor.

Coating

Standard epoxy paint, others be available on request.

Variable colors