Home Product Disconnector Double Break Disconnector

DisconnectorDouble Break Disconnector

General Description
  • IEC 62271, ANSI/IEEE Std C37, NEMA

  • ISO 9001, KEMA, CESI, CE, TUV, UL, ASTA

  • Seismic design, ETGI-1.020, IEEE Std 693, NCh2369

  • Structural design, ASTM A325, ANSI/AISC 360, AWS D1.1

  • High altitude correction per IEC 62271 & IEEE C37, ~ 5000m

  • Stationary Cast Aluminum Contact Base

  • Copper and Silver Moving Contact

  • Robust, Seamless Steel Pipe Base

Typical Specification

Double Break Disconnector 126~363kV

GW7

Unit

GW7-126

GW7-145

GW7A-252

GW7-363

Rated voltage

kV

126

145

252

363

Rated Frequency

Hz

50\60

50\60

50\60

50\60

Rated current

A 

1250~3150

2000~3150

3150~5000

3150~5000

Rated short-time withstand current and duration

kA/s

40/3

40/3

50/3, 63/3

63/3

Rated peak withstand current

kA

100

100

125, 160

160

Rated short-time power

frequency withstand voltage(rms)

To earth

kV

230

275

460

510

Across Breaks

kV

265

315

530

580

Rated lightning impulse

withstand voltage(peak)

To earth

kV

550

650

1050

1175

Across Breaks

kV

630

750

1200

1175+205

Rated switching impulse

withstand voltage

To earth

kV

-

-

-

950

Across Breaks

kV

-

-

-

850+295

Switching capacitive current

A

1

1

2

1

Switching inductive current

A

0.5

0.5

1

0.7

Rated busbar transferring current

A

-

-

2000

1600