Home Product Disconnector Center Break Disconnector

DisconnectorCenter Break Disconnector

General Description
  • IEC 62271, ANSI/IEEE Std C37, NEMA

  • ISO 9001, KEMA, CESI, CE, TUV, UL, ASTA

  • Seismic design, ETGI-1.020, IEEE Std 693, NCh2369

  • Structural design, ASTM A325, ANSI/AISC 360, AWS D1.1

  • High altitude correction per IEC 62271 & IEEE C37, ~ 5000m

  • Flexible contacting outgoing base

  • Strong current flow in conductive rod contact finger

  • Accurate transmission and ease of commission

Typical Specification

Center Break Disconnector 40.5~252kV

GW4/GW5

Unit

GW4-40.5

GW4-72.5

GW4-126

GW4-145

GW4-252

GW5-72.5

GW5-126

Rated voltage

kV

40.5

72.5

126

145

252

72.5

126

Rated Frequency

Hz

50\60

50\60

50\60

50\60

50\60

50\60

50\60

Rated current

A 

 2500~4000

 2000~4000

 1250~3150

 2000~3150

 2500~4000

2500

2000

Rated short-time withstand current and duration

kA/s

40/3,50/3

40/3,50/4

40/3

40/3,50/3

50/3,63/3

40/3

40/3

Rated peak withstand current

kA

100,125

100,125

100

100,125

125,160

100

100

Rated short-time power

frequency withstand voltage(rms)

To earth

kV

95

160,181

230

275

460

160

230

Across Breaks

kV

118

200,226

230+70

315

530

200

230+73

Rated lightning impulse

withstand voltage(peak)

To earth

kV

185

350,396

550

650

1050

350

550

Across Breaks

kV

215

410,463

550+100

750

1200

410

550+103

Rated busbar transferring current

A

1600

1600

1600

1600

2000

1600

1600