Home Product Circuit Breaker Indoor Vacuum Circuit Breaker (VCB)

Circuit BreakerIndoor Vacuum Circuit Breaker (VCB)

General Description
  • IEC 62271, ANSI/IEEE Std C37, NEMA

  • ISO 9001, KEMA, CESI, CE, TUV, UL, ASTA

  • Seismic design, ETGI-1.020, IEEE Std 693, NCh2369

  • Structural design, ASTM A325, ANSI/AISC 360, AWS D1.1

  • High altitude correction per IEC 62271 & IEEE C37, ~ 5000m

  • Highly reliable vacuum interrupter embedded in the pole

  • Modular operating mechanism with higher mechanical life

  • Optional for fixed and withdrawable version

  • Optional accessory for 2nd Trip Coil 

Typical Specification

Indoor Medium Voltage AC Vacuum Circuit Breaker

Item

Unit

Data

Rated voltage

kV

7.2/12

15/17.5/24

33/36/40.5

Rated current

A

630,1250,1600,2000,

2500,3150,4000

630,1250,1600,2000,

2500,3150,4000

1250,1600,2000,

2500,3150

Rated frequency

Hz

50/60

50/60

50/60

Rated insulation level





 Rated power frequency withstand voltage/1min 

kV

42

65

95

 Rated lighting impulse withstand voltage - BIL

kV

75

125

185

Rated short circuit breaking current

kA

20/25/31.5/40/50

20/25/31.5/40

25/31.5/40

Rated short time withstand current(4s)

kA

20/25/31.5/40/50

20/25/31.5/40

25/31.5/40

Rated peak value withstand current

kA

50/63/80/125/137

50/63/80/100

63/80/100

Breaking current of capacitor bank*

A

-

-

630

Operating mechanism type


Motor drive spring mechanism

Rated operating sequence


Isc < 40kA: O-0.3s-CO-180s-CO

Isc = 40kA: O-180s-CO-180s-CO

Rated short-circuit current breaking times/ electrical endurance

level

E2 (IEC62271-100)

Mechanical endurance

times

20000

20000

20000

Rated auxiliary control voltage

V

AC220/110, DC220/110

Opening time

ms

20~50

20~50

20~60

Arcing time

ms

10~15

10~15

≤ 15

Full opening time

ms

30~65

30~65

30~65

Closing time

ms

35~70

35~70

35~70